MACX MCR-UI-UI-UP-NC 数据手册
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Isolating amplifier with safe electrical isolation and wide-range power supply (24 V ... 230 V AC/DC). DIP
switches on the front, over 1600 signal conversions can be set. Standard configuration (IN 0 ... 10 V/OUT 0 ...
20 mA), screw connection, SIL.
Product Features
■
■
■
■
■
■
■
■
■
■
Over 1600 signal conversions can be set via DIP switches on the front
Up to SIL 2 according to EN 61508
Installation in zone 2 permitted
Analog signal conditioner for isolating, filtering, amplifying, and converting standard analog signals
Configurable input and output signals including bipolar current and voltage signals
Status indicator for supply voltage
Wide-range power supply of 19.2 ... 253 V AC/DC
Plug-in screw or spring-cage connection technology (Push-in technology)
3-way electrical isolation
Active or passive output
Key Commercial Data
Packing unit
1 pc
GTIN
Weight per Piece (excluding packing)
167.2 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
05/09/2016 Page 1 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Technical data
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m
Degree of protection
IP20
Input data
Number of inputs
1
Voltage input signal
0 mV ... 50 mV
0 mV ... 60 mV
0 mV ... 75 mV
0 mV ... 100 mV
0 mV ... 120 mV
0 mV ... 150 mV
0 mV ... 200 mV
0 mV ... 300 mV
0 mV ... 500 mV
0 V ... 1 V
0 V ... 1.5 V
0 V ... 2 V
0 V ... 3 V
0 V ... 5 V
0 V ... 10 V (Configurable via DIP switches)
0 V ... 15 V
0 V ... 20 V
0 V ... 30 V
0 V ... 50 V
0 V ... 100 V
-50 mV ... 50 mV
-60 mV ... 60 mV
-75 mV ... 75 mV
-100 mV ... 100 mV
-120 mV ... 120 mV
-150 mV ... 150 mV
-200 mV ... 200 mV
-300 mV ... 300 mV
-500 mV ... 500 mV
-1 V ... 1 V
05/09/2016 Page 2 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Technical data
Input data
-1.5 V ... 1.5 V
-2 V ... 2 V
-3 V ... 3 V
-5 V ... 5 V
-10 V ... 10 V
-15 V ... 15 V
-20 V ... 20 V
-30 V ... 30 V
-50 V ... 50 V
-100 V ... 100 V
1 V ... 5 V
2 V ... 10 V
Current input signal
0 mA ... 1 mA (Configurable via DIP switches)
0 mA ... 1.5 mA
0 mA ... 2 mA
0 mA ... 3 mA
0 mA ... 5 mA
0 mA ... 10 mA
0 mA ... 15 mA
0 mA ... 20 mA
0 mA ... 30 mA
0 mA ... 50 mA
0 mA ... 100 mA
-1 mA ... 1 mA
-1.5 mA ... 1.5 mA
-2 mA ... 2 mA
-3 mA ... 3 mA
-5 mA ... 5 mA
-10 mA ... 10 mA
-15 mA ... 15 mA
-20 mA ... 20 mA
-30 mA ... 30 mA
-50 mA ... 50 mA
-100 mA ... 100 mA
1 mA ... 5 mA
2 mA ... 10 mA
4 mA ... 20 mA
Max. input voltage
± 100 V
Max. input current
± 100 mA
Input resistance of voltage input
approx. 1 MΩ (± 1 V DC ... ± 100 V DC)
05/09/2016 Page 3 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Technical data
Input data
Input resistance current input
approx. 10 Ω (± 10 mA DC ... ± 100 mA DC)
Output data
Number of outputs
1
Configurable/programmable
Yes, can be switched
Voltage output signal
0 V ... 10 V (Configurable via DIP switches)
0 V ... 5 V
2 V ... 10 V
1 V ... 5 V
-10 V ... 10 V
-5 V ... 5 V
0 V ... 2.5 V
0.5 V ... 2.5 V
-2.5 V ... 2.5 V
Current output signal
0 mA ... 5 mA
0 mA ... 10 mA
0 mA ... 20 mA (Configurable via DIP switches)
1 mA ... 5 mA
2 mA ... 10 mA
4 mA ... 20 mA
-5 mA ... 5 mA
-10 mA ... 10 mA
-20 mA ... 20 mA
Max. output voltage
15 V
Max. output current
35 mA
Load/output load voltage output
≥ 1 kΩ (10 V)
Load/output load current output
≤ 600 Ω (20 mA; active)
passive: ≤ (UB-2 V) / Ioutmax
Power supply
Supply voltage range
24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
8 mm
Screw thread
M3
05/09/2016 Page 4 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Technical data
Connection data
Connection method
COMBICON
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (Compared to the final value)
Maximum temperature coefficient
0.0075 %/K
Limit frequency (3 dB)
10 kHz (Can be switched to 30 Hz)
Alignment zero
±4%
Alignment span
±4%
Step response (10-90%)
35 µs (at 10 kHz)
11 ms (At 30 Hz)
Protective circuit
Transient protection
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
300 V AC
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PA 66-FR
Mounting position
any
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc
IECEx
Ex nA IIC T4 Gc
UL, USA / Canada
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC
Functional Safety (SIL)
SIL 2
Safety characteristic data
Integrity requirement
IEC 61508 - Low demand
Designation
Input isolator (live zero signals)
Architecture
Single-channel, 1oo1
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
85.9 %
MTBF
231 Years
λSU
3.7 x 10 (370 FIT)
λSD
0
λDU
6 x 10 (60 FIT)
λDD
0
Probability of a hazardous failure on demand (PFDAVG)
2.7 x 10 (1 year)
-7
-8
-4
05/09/2016 Page 5 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Technical data
Safety characteristic data
Diagnostic coverage (DC)
0%
Integrity requirement
IEC 61508 - Low demand
Designation
Output isolator (live zero signals)
Architecture
Single-channel, 1oo1
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
82.7 %
MTBF
233 Years
λSU
3.5 x 10 (350 FIT)
λSD
0
λDU
7.3 x 10 (73 FIT)
λDD
0
Probability of a hazardous failure on demand (PFDAVG)
3.2 x 10 (1 year)
Diagnostic coverage (DC)
0%
Integrity requirement
IEC 61508 - High demand
Designation
Input isolator (live zero signals)
Architecture
Single-channel, 1oo1
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
85.9 %
MTBF
231 Years
λSU
3.7 x 10 (370 FIT)
λSD
0
λDU
5.97 x 10 (59.7 FIT)
λDD
0
Probability of a hazardous failure per hour (PFHD)
6.0 x 10
Diagnostic coverage (DC)
0%
Integrity requirement
IEC 61508 - High demand
Designation
Output isolator (live zero signals)
Architecture
Single-channel, 1oo1
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
82.7 %
MTBF
233 Years
λSU
3.5 x 10 (350 FIT)
λSD
0
λDU
7.3 x 10 (73 FIT)
λDD
0
Probability of a hazardous failure per hour (PFHD)
7.3 x 10
-7
-8
-4
-7
-8
-8
-7
-8
-8
05/09/2016 Page 6 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Technical data
Safety characteristic data
Diagnostic coverage (DC)
0%
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc
IECEx
Ex nA IIC T4 Gc
UL, USA / Canada
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 2.0
EC001485
ETIM 3.0
EC001485
ETIM 4.0
EC002653
ETIM 5.0
EC002653
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / EAC / cULus Listed
05/09/2016 Page 7 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Approvals
Ex Approvals
IECEx / ATEX / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
Functional Safety
EAC
cULus Listed
Drawings
Dimensional drawing
99
Block diagram
12,5
US
4-wire
[mA]
114,5
4-wire
[mV]
4.2
4.2
5.2
5.2
5.1
US
4-wire
[V]
PLC / DCS
4.1
5.2
4.1
US
OUT
IN
Sensor / Field
5.1
5.2
±50 mV... ±1000 mV
±1 mA... ±5 mA
±10 mA... ±100 mA
active
2.2
2.2
2.1
active
2.1
+
GND
±1 V... ±100 V
3.1
3.2 passive
+
3.1
3.2
+
passive
Power
24V ...230V AC/DC
1.2
1.1
Zone 2
Div. 2
05/09/2016 Page 8 / 9
https://www.phoenixcontact.com/in/products/2811297
Signal conditioner - MACX MCR-UI-UI-UP-NC - 2811297
Application drawing
MACX MCR-UI-UI-UP
IN
Level sensor
4.2
0...20mA
24V
4.1
5.2
5.1
OUT
±50mV... ±1000mV
±1mA... ±5mA
–
active
±10mA... ±100mA
+
GND
3.2
3.1
2.2
passive
±1V... ±100V
2.1
Power
24V ...230V AC/DC
1.2
≃
1.1
Control system
Power
24V ...230V AC/DC
Level measurement with analog input terminals (active input card)
Application drawing
MACX MCR-UI-UI-UP
M
IN
4.2
Shunt
resistor
mV
4.1
5.1
–
±10mA... ±100mA
–
active
+
3.2
D
3.1
AI2
5.2
+
OUT
±50mV... ±1000mV
±1mA... ±5mA
GND
±1V... ±100V
2.2
passive
1
2.1
Power
24V ...230V AC/DC
2
1
1
2
2
3
3
4
4
1.2
≃
1.1
Battery
Power
24V ...230V AC/DC
Shunt measurement and Inline terminal with analog input channels within an Inline station (passive input card)
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
05/09/2016 Page 9 / 9
MACX MCR-UI-UI-UP-NC 价格&库存
很抱歉,暂时无法提供与“MACX MCR-UI-UI-UP-NC”相匹配的价格&库存,您可以联系我们找货
免费人工找货